Features:
-
LEL Detection Available for Many Gases
-
2 Alarm levels
-
Stand Alone System
-
Input Voltages: 24 VDC Standard, 115 VAC or 48 VDC (optional)
-
Audible and Visual Alarms
-
Compact Design
-
Simple Installation
-
AC Version Equipped with Power Cord
-
Relay Contacts Rated 12A @ 115 VAC
-
Low Maintenance
Application/s
-
Battery Storage and Charging Locations
-
Petrochemical Plants
-
Refineries
-
Water & Wastewater Treatment Plants
-
Gas, Telephone, and Electric Utilities
-
Manufacturing Facilities
-
Steel
-
Automotive
-
HVAC
-
Buildings on Landfill
Overview:
A perfect low cost solution for hydrogen detection in battery rooms, or for LEL level detection of a variety of flammable or solvent vapours in general industry. The Model PS 2 is a multipurpose gas monitor utilising a MOS (metal oxide sensor) for long lasting and low maintenance detection of LEL levels of many gases or vapours.
The PS 2 has two alarm levels for increasing gas or vapour levels. Inquire at the factory for your specific requirement. Each alarm level activates a 12 amp relay inside the unit, and terminals are provided for wiring the relay to activate an external alarm device or some other device such as a ventilation fan.
This stand alone unit is housed in a durable plastic enclosure with flanges provided for wall mounting and is designed with easy access wiring hubs on the bottom of the unit. The front of the PS 2 contains three lights; Pilot, Alarm 1, and Alarm 2. An internal audible alarm (85 db) activates in a gas alarm condition, and alarm relays are activated.
The standard PS 2 is supplied with the gas sensor located on the end of a 30 foot cable (other cable lengths are also available). Power options include 24 VDC as standard, with 115 VAC or 48 VDC versions available, and the AC version comes complete with a 6′ power cord. For use in non hazardous locations only.
Specifications:
Outputs | |
Relays | 12 amp rated contacts for each alarm |
Audible | 85 db alarm at 10 cm |
Visual | Alarm 1: Orange LED
Alarm 2: Red LED |
Environmental | |
Operating
Temp |
2°C to 49°C |
Relative Humidity | 10 – 95% RH, non condensing |
Physical | |
Dimensions |
Height 174 mm
Width 165 mm Depth 84 mm |
Enclosure | ABS plastic, indoor housing |
Sensors | |
Sensor Types | Metal Oxide Semiconductor type (MOS) |
Measuring Ranges |
LEL levels available for many gases. Typically set to 10% LEL for alarm 1,
and 25% or 30% LEL for alarm 2 (Highest possible setting is 30% LEL). |
Sensor Connector | Sensor is connected to 30ʼ extension cable wired to terminals inside unit. Cable length can be decreased or increased as needed. |
Power | 24 VDC (standard)
115 VAC or 48 VDC (optional) |
Warranty | One year materials and workmanship |
- Overview
-
Overview:
A perfect low cost solution for hydrogen detection in battery rooms, or for LEL level detection of a variety of flammable or solvent vapours in general industry. The Model PS 2 is a multipurpose gas monitor utilising a MOS (metal oxide sensor) for long lasting and low maintenance detection of LEL levels of many gases or vapours.
The PS 2 has two alarm levels for increasing gas or vapour levels. Inquire at the factory for your specific requirement. Each alarm level activates a 12 amp relay inside the unit, and terminals are provided for wiring the relay to activate an external alarm device or some other device such as a ventilation fan.
This stand alone unit is housed in a durable plastic enclosure with flanges provided for wall mounting and is designed with easy access wiring hubs on the bottom of the unit. The front of the PS 2 contains three lights; Pilot, Alarm 1, and Alarm 2. An internal audible alarm (85 db) activates in a gas alarm condition, and alarm relays are activated.
The standard PS 2 is supplied with the gas sensor located on the end of a 30 foot cable (other cable lengths are also available). Power options include 24 VDC as standard, with 115 VAC or 48 VDC versions available, and the AC version comes complete with a 6′ power cord. For use in non hazardous locations only.
- Specifications
-
Specifications:
Outputs Relays 12 amp rated contacts for each alarm Audible 85 db alarm at 10 cm Visual Alarm 1: Orange LED Alarm 2: Red LED
Environmental Operating Temp
2°C to 49°C Relative Humidity 10 – 95% RH, non condensing Physical Dimensions
Height 174 mm Width 165 mm
Depth 84 mm
Enclosure ABS plastic, indoor housing Sensors Sensor Types Metal Oxide Semiconductor type (MOS) Measuring Ranges
LEL levels available for many gases. Typically set to 10% LEL for alarm 1, and 25% or 30% LEL for alarm 2 (Highest possible setting is 30% LEL).
Sensor Connector Sensor is connected to 30ʼ extension cable wired to terminals inside unit. Cable length can be decreased or increased as needed. Power 24 VDC (standard) 115 VAC or 48 VDC (optional)