Features:
- Digital processing of the measurement values incl. temperature compensation
- Continuous monitoring
- Low zero point drift
- Good stability to poisoning
- Long-life sensor
- Modular plug-in technology
- Easy maintenance
- Comfortable calibration with selective access release
- Reverse polarity protected, overload and short-circuit proof
- (0) 4 – 20 mA / (0) 2 – 10V analog signal output, selectable
- Serial interface RS-485
- IP65 protected
- Manual calibration via potentiometer (option)
- Manual addressing for RS-485 mode (option)
- 4 – 20 mA analog input for an external AT transmitter (optional)
- Approved according to EN 61010-1; ANSI/UL 61010 1; CAN/CSA-C22.2 No. 61010-1
- Optional: relay output / integrated buzzer / LED flashlight
Application/s:
- Electronic control
- Automation system
CH2O transmitter including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air to detect formaldehyde concentrations. Integrated in the transmitter there is a comfortable calibration routine with selective access release. The ADT-53 possesses a standard analog output (0) 4- 20 mA or (0) 2– 10 V DC, and an RS-485 interface. 2 relays with adjustable switching thresholds are available as an option.
For the detection of formaldehyde within a wide range of industrial and commercial applications. Due to the standard output signal and the RS-485 interface the CH2O transmitter is compatible to the PolyGard Gas Controller series MGC and DGC by MSR-E as well as to any other electronic control or automation system.
Specifications:
Detected gas | Formaldehyde (CH2O) |
Sensor element | Electrochemical, diffusion |
Measuring range | 0 – 10 ppm (factory set)
adjustable from 0 – 5 to 0 – 10 ppm |
Temperature range | -10 °C to + 45 °C w/o heating |
Pressure range | Atmospheric ± 15 % |
Humidity range | Atmospheric ± 15 %
15 – 90 % RH non-condensing (abrupt change of the relative humidity may cause a short-time sensor signal) |
Storage temperature | 5 °C to 30 °C |
Storage time | Max. 3 months |
Mounting height | 0.3 to 0.8 m |
Accuracy | 0.01 ppm |
Repeatability | < 2 % of reading |
Long-term output drift | < 2% signal loss/month |
Response time | t90 < 50 sec. |
Sensor life expectancy | > 3 years/normal operating environment |
Cross sensitivity1 | Reaction (%) |
Carbon monoxide; CO | 10 -18 % |
Hydrogen, H2 | 1 – 3 % |
- Overview
-
CH2O transmitter including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air to detect formaldehyde concentrations. Integrated in the transmitter there is a comfortable calibration routine with selective access release. The ADT-53 possesses a standard analog output (0) 4- 20 mA or (0) 2– 10 V DC, and an RS-485 interface. 2 relays with adjustable switching thresholds are available as an option.
For the detection of formaldehyde within a wide range of industrial and commercial applications. Due to the standard output signal and the RS-485 interface the CH2O transmitter is compatible to the PolyGard Gas Controller series MGC and DGC by MSR-E as well as to any other electronic control or automation system.
- Specifications
-
Specifications:
Detected gas Formaldehyde (CH2O) Sensor element Electrochemical, diffusion Measuring range 0 – 10 ppm (factory set) adjustable from 0 – 5 to 0 – 10 ppm
Temperature range -10 °C to + 45 °C w/o heating Pressure range Atmospheric ± 15 % Humidity range Atmospheric ± 15 % 15 – 90 % RH non-condensing
(abrupt change of the relative humidity may
cause a short-time sensor signal)
Storage temperature 5 °C to 30 °C Storage time Max. 3 months Mounting height 0.3 to 0.8 m Accuracy 0.01 ppm Repeatability < 2 % of reading Long-term output drift < 2% signal loss/month Response time t90 < 50 sec. Sensor life expectancy > 3 years/normal operating environment Cross sensitivity1 Reaction (%) Carbon monoxide; CO 10 -18 % Hydrogen, H2 1 – 3 % - Downloads
-