Features:
• Electrochemical, Infrared, Catalytic Bead or PID Sensor Element
• Wired Powered (3-Wire), 12 to 35 VDC Operating Voltage
• Operating Temperature Range of -40oc to + 54°c • Graphical LCD with LED Backlight
• 3 Push-Button Interface (ADD, MENU, SUB) with 3 Corresponding Magnetic, Non-Intrusive Switches
• 2 Individually Configurable Alarm Set-Points: Two Front Panel LED Indicators (Amber and Red); Optional 2 Dry-Contact Relays
• Output Options: 4-20 mA (3-Wire) Analog, RS-485 Modbus, Optional GEN II 900 MHz or GEN II 2.4 GHz Radio
• Sensor Element Warranty Subject to Verification
• 1-Year Limited Hardware Warranty
Application/s:
• Blast Mining
• Petrochemical plants
• Refineries
• Water & wastewater treatment plants
• Gas, telephone & electric utilities
• Manufacturing facilities
• Laboratories
Overview:
The OI-6000 Series Ambient Explosion Proof Air Hazardous Gas Detector is a versatile assembly that uses an electrochemical, infrared, catalytic bead or PID sensor element to detect a variety of gases. Wired powered (12 to 35 VDC) with 4-20 mA analog and RS-485 Modbus outputs standard. Magnetic switches allow for non-intrusive calibration while in the field as well as full system settings and diagnostics.
Specifications:
Sensor Type | Eletrochemical, Infrared, Catalytic Bead or PID |
Operating Voltage | Wired Powered (3-Wire) 12 to 35 VDC |
Power Draw | 2 Watts Maximum |
Protection | Power Eletromagnetic Interference (EMI) Filter 4-20 mA Surge SuppressionRS-485 Surge Suppression |
Display Screen | 102×64 Resolution Graphical LCD Screen
Transflective (Sunlight Readable) with |
Interface | 3 Push-Buttons (MENU, ADD and SUB)
3 Magnetic, Non-Intrusive Switches |
Customizable Settings | 2 Individually-Configurable Alarm LED/Relay Set-Points |
Tamb Temperature Range | -40°C to +54°C |
Output (Digital) | RS-485 Modbus |
Wired (Analog) Output | 4-20 mA (3-Wire)
Fault Terminal Optional 2 Dry-Contact Relays with |
Remote Sensor Kit
(Optional Additional Feature) |
OI-501-5 Remote Sensor Kit with Enclosure (5 Pin)• Electrochemical Sensor Max. Length: 250 Feet• Infrared Sensor Max. Length: 40 Feet• PID Sensor Max. Length: 35 Feet• Catalytic Bead Sensor Max. Length: 15 Feet |
Product Dimensions | 5.5 in. T x 6 in. W x 7 in. H (8 in. W x 17 in. H Max. with Attachments) |
Total Weight | 6 lbs. |
Hazardous Location
Certifications and Approvals |
CSA
Class I, Division 1, Groups C & D Ex d IIB T6 Gb Class I, Zone 1, AEx db IIB T6 Gb Tamb -400C to +54oC
ATEX Models w/ Radio Option II 2 (1) G Ex db mb ia [ia Ga] IIB T6 Gb
Models w/out Radio Option II2G Ex db mb IIB T6 Gb
IECEx Models w/ Antenna Fitting Ex db mb ia [ia Ga] IIB T6 Gb -400C < Ta < +540C
Models w/out Antenna Fitting Ex db mb IIB T6 Gb -40oC < Ta < +54oC |
Hardware Warranty | 1-Year, Limited |
Sensor Element Warranty | Varies with Gas Type |
Part Number Formula | OI-6000-[Sensor Type]-[Gas]-[Radio Option]-[Relay Option]-
OI-6000-X-X-X-X-O |
- Overview
-
Overview:
The OI-6000 Series Ambient Explosion Proof Air Hazardous Gas Detector is a versatile assembly that uses an electrochemical, infrared, catalytic bead or PID sensor element to detect a variety of gases. Wired powered (12 to 35 VDC) with 4-20 mA analog and RS-485 Modbus outputs standard. Magnetic switches allow for non-intrusive calibration while in the field as well as full system settings and diagnostics.
- Specifications
-
Specifications:
Sensor Type Eletrochemical, Infrared, Catalytic Bead or PID Operating Voltage Wired Powered (3-Wire) 12 to 35 VDC Power Draw 2 Watts Maximum Protection Power Eletromagnetic Interference (EMI)
Filter 4-20 mA Surge SuppressionRS-485 Surge SuppressionDisplay Screen 102×64 Resolution Graphical LCD Screen Transflective (Sunlight Readable) with
White LED BacklightInterface 3 Push-Buttons (MENU, ADD and SUB) 3 Magnetic, Non-Intrusive Switches
for CalibrationCustomizable Settings 2 Individually-Configurable Alarm LED/Relay Set-Points Tamb Temperature Range -40°C to +54°C Output (Digital) RS-485 Modbus Wired (Analog) Output 4-20 mA (3-Wire) Fault Terminal
Optional 2 Dry-Contact Relays with
Replaceable 4 Amp FusesRemote Sensor Kit (Optional Additional Feature)
OI-501-5 Remote Sensor Kit with Enclosure
(5 Pin)• Electrochemical Sensor Max. Length: 250 Feet• Infrared Sensor Max. Length: 40 Feet• PID Sensor Max. Length: 35 Feet• Catalytic Bead Sensor Max. Length: 15 FeetProduct Dimensions 5.5 in. T x 6 in. W x 7 in. H
(8 in. W x 17 in. H Max. with Attachments)Total Weight 6 lbs. Hazardous Location Certifications and Approvals
CSA Class I, Division 1, Groups C & D Ex d IIB T6 Gb
Class I, Zone 1, AEx db IIB T6 Gb Tamb -400C to +54oC
ATEX
Models w/ Radio Option
II 2 (1) G
Ex db mb ia [ia Ga] IIB T6 Gb
Ta= -40°C to + 54°CModels w/out Radio Option
II2G
Ex db mb IIB T6 Gb
Ta= -400c to + 54ocIECEx
Models w/ Antenna Fitting Ex db mb ia [ia Ga] IIB T6 Gb -400C < Ta < +540C
Models w/out Antenna Fitting Ex db mb IIB T6 Gb -40oC < Ta < +54oC
Hardware Warranty 1-Year, Limited Sensor Element Warranty Varies with Gas Type Part Number Formula OI-6000-[Sensor Type]-[Gas]-[Radio Option]-[Relay Option]- OI-6000-X-X-X-X-O
- Downloads
-