| ELECTRICAL |
|
| Power supply |
18–29 V DC, reverse-polarity protect.; |
| 18–27 V AC (only for output signal 2–10 V) |
| Power consumption |
23 mA, max. (0.6 VA for 24 V) |
| Analog output signal |
Proportional, overload and short-circuit proof, |
| load ≤ 500 Ω for current signal, ≥ 50 kΩ for voltage signal |
| 4–20 mA or 2–10 V = measuring range |
| 3–4 mA or 1.5–2 V = underrange |
| > 20–21.2 mA or 10–10.6 V = overrange |
| 2 mA or 1 V = fault |
| > 21.8 mA or 10.9 V = fault High |
| SENSOR ELEMENT |
|
| Gas type and measuring range |
See Ordering Information |
| Measuring principle |
Electrochemical |
| Poisoning |
Electrochemical sensor elements are susceptible to poisoning by organic solvents. |
| RECOMMENDED STORAGE CONDITIONS |
| Storage temperature range1 |
See following tables |
| Storage time1 |
Ca. 6 months |
| Humidity range / pressure range |
See following tables |
| PHYSICAL |
|
| Housing type P |
Polycarbonate UL 94 V2 |
| Housing colour |
Similar to RAL 7035 (light grey) |
| Dimensions (Ø x H) |
24 x 22 mm (0.94 x 0.87 in.) |
| Weight |
Ca. 30 g (0.066 lb) |
| Protection class |
IP65 |
| Mounting |
Screw mounting, external thread M25 x 1.5 mm |
| Wire connection |
Screw-type terminal, 0.25–1.3 mm2, 3-pin |
| REGULATIONS |
|
| Directives |
EMC directives 2014/30/EU, |
| UL2075 (only for sensor MC2-X-E1110-E-X-P) |
| CE, UKCA |
| Compliance with: |
| EN 378 |
| EN 45544-1, -3 |
| EN 50104 (for O2) |
| EN 50271, |
| EN 50545 |
| EN 61010-1:2010 |
| ANSI/UL 61010-1 |
| CAN/CSA-C22.2 No. 61010-1 |
| Warranty |
1 year on sensors (not if poisoned or overloaded) |
| OPTIONS |
|
| HOUSING TYPE A |
|
| Material / flammability classification |
Polycarbonate / UL 94 V2 |
| Housing colour |
RAL 7032 (light grey) |
| Dimensions (B x H x D) |
94 x 130 x 57 mm (3.7 x 5.1 x 2.2 in.) |
| Weight / package volume |
Ca. 0,2 kg (0.4 lb) / ca. 4,5 l |
| Protection class |
IP65 |
| Mounting |
Wall mounting |
| Pre-embossing for cable entry / sensor |
6 x M20/M25 |
| DISPLAY |
|
| LC Display |
2 lines, 16 characters each, monochrome |
| Temperature range |
-20 °C to +60 °C (-4 °F to 140 °F) |
| OPEN-COLLECTOR |
|
| Transistor output (2) |
For horn (resettable) and warning lamp |
| Switching capacity |
24 V DC / 50 mA (+ switching) |