Features:
- Low cost versatile solution
- Capable of up to 8 separate channels
- Digital display of all 8 channels simultaneously
- Compact, weatherproof, NEMA 4X enclosure
- 240 VAC or 24 VDC operation
- Long life sensors (2+ years typical)
- Accepts any 4-20 mA transmitter
- Audible alarm with reset button
- Two programmable alarm levels per channel
- Common alarm and fail relays
- Relay rating 10 amps, form C
- View min/max reading
- Adjustable timer delay on/off
Application/s:
- Petrochemical plants
- Refineries
- Water & wastewater treatment plants
- Pulp & paper mills
- Gas, telephone & electric utilities
- Parking garages
- Manufacturing facilities
- Steel
- Automotive
Overview:
The Beacon 800 is a versatile, low cost fixed system Gas detection controller for one to eight points of gas detection. The 2 large digital displays have backlighting and easily identify both the gas type and the gas concentration for all 8 channels simultaneously. The Beacon 800 is housed in a NEMA 4X rated case for a weather tight seal.
The Beacon 800 is microprocessor controlled and is capable of accepting up to 8 separate 4-20 mA sensor transmitters which can be either 2 or 3 wire. The Beacon 800 can be powered by either 24 VDC or 240 VAC. It is simple to operate and comes complete with a wall mount installation kit.
The case design complies with the new lock out/tag out standard and can be fully secured. An external reset switch allows alarms to be silenced from outside the controller housing. The bottom mounted siring hubs allow for easy wiring.
With 10 amp rated relays, the Beacon 800 can be wired directly to a variety of devices like alarm horns, buzzers or lights. This eliminates the need for costly external relays from the controller to devices.
Specifications:
Physical | |
Dimensions: | Height 318mm Width 279 mm Depth: 163 mm |
Enclosure: | Wall mounting grey polycarbonate with hinged cover. |
Conduit Connection: | 3/4” NPT conduit hubs, 4 provided for sensors, power and relay wiring. |
Wiring Termination: | Screw type terminal block 14 gauge max. |
Environmental | |
Operating Temp: | -20°C to 50°C |
Storage Temp: | -20°C to 70°C |
Relative Humidity: | 0 –100% RH |
Enclosure Rating: | NEMA-4X enclosure, waterproof, chemical and weather resistant. |
Inputs | |
4-20 mA | Accepts any 4-20 mA transmitters (24 VDC, 2 or 3 wire). Wiring distances up to 1,500 metres. |
Sampling methods: | Diffusion and sample draw heads available. Carbon Monoxide (CO) 0 – 150 ppm, Combustibles 0 -100% LEL, Nitrogen Dioxide (NO2) 0 – 15.0 ppm (Refer to list of detectable Gases for additional ranges). |
Outputs | |
Relays: | 2 relays per channel 10 amp rating, SPDT isolated contacts. 1 set of common relays: 2 for gas alarm levels, 1 for malfunction. Relays fully programmable for: increasing or decreasing alarms, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off. |
24 VDC: | 24 VDC output provided to operate sample draw adapters or other accessories |
Display: | 2 alphanumeric displays with backlighting. 16 characters per line; 4 lines each. All 8 channels continuously displayed. |
Audible: | Built-in audible alarm, 94 dB, mounted on enclosure. Coded output: Pulsing = gas alarm, Steady = fail |
Visual: | 4 visual LED alarms on front cover for alarm indications, pilot and malfunction. |
Optional Expansion Cards: | Individual 4-20 mA (or 1-5 VDC) outputs. Heavy duty relay card (4 each @ 30 amps). |
Power: | 240 VAC or 24 VDC. Optional – _115 VAC. Battery backup option available. |
Warranty: | One years materials and workmanship. |
Gases Detected:
Ammonia (NH3) | 0 – 75.0 ppm |
Arsine (AsH3) | 0 – 0.2 ppm |
Boron Trichloride (BCl3) | 0 – 15.0 ppm |
Carbon Dioxide (CO2) | 0 – 1.0 % |
Carbon Monoxide (CO) | 0 – 300 ppm |
Chlorine (Cl2) | 0 – 3.0 ppm |
Chlorine Dioxide (ClO2) | 0 – 1.0 ppm |
Chlorine Trifluoride (CIF3) | 0 – 1.0 ppm |
Combustibles | 0 – 100% LEL |
Diborane (B2H6) | 0 – 30.0 ppm |
Fluorine (F2) | 0 – 5/15 ppm |
Hydrogen (H2) | 0 – 2000 ppm |
Hydrogen Chloride (HCl) | 0 – 15.0 ppm |
Hydrogen Fluoride (HF) | 0 – 9.0 ppm |
Hydrogen Sulfide (H2S) | 0 – 100.0 ppm |
Nitric Oxide (NO) | 0 – 100.0 ppm |
Nitrogen Dioxide (NO2) | 0 – 15.0 ppm |
Nitrogen Trifluoride (NF3) | 0 – 30.0 ppm |
Oxygen (O2) | 0 – 25.0% |
Ozone (O3) | 0 – 1.0 ppm |
Phosphine (PH3) | 0 – 1.0 ppm |
Silane (SiH4) | 0 – 15.0 ppm |
Sulphur Dioxide (SO2) | 0 – 30.0 ppm |
TEOS (Si(OC2H5)4) | 0 – 15/30 ppm |
- Overview
-
Overview:
The Beacon 800 is a versatile, low cost fixed system Gas detection controller for one to eight points of gas detection. The 2 large digital displays have backlighting and easily identify both the gas type and the gas concentration for all 8 channels simultaneously. The Beacon 800 is housed in a NEMA 4X rated case for a weather tight seal.
The Beacon 800 is microprocessor controlled and is capable of accepting up to 8 separate 4-20 mA sensor transmitters which can be either 2 or 3 wire. The Beacon 800 can be powered by either 24 VDC or 240 VAC. It is simple to operate and comes complete with a wall mount installation kit.
The case design complies with the new lock out/tag out standard and can be fully secured. An external reset switch allows alarms to be silenced from outside the controller housing. The bottom mounted siring hubs allow for easy wiring.
With 10 amp rated relays, the Beacon 800 can be wired directly to a variety of devices like alarm horns, buzzers or lights. This eliminates the need for costly external relays from the controller to devices.
- Specifications
-
Specifications:
Physical Dimensions: Height 318mm Width 279 mm Depth: 163 mm Enclosure: Wall mounting grey polycarbonate with hinged cover. Conduit Connection: 3/4” NPT conduit hubs, 4 provided for sensors, power and relay wiring. Wiring Termination: Screw type terminal block 14 gauge max. Environmental Operating Temp: -20°C to 50°C Storage Temp: -20°C to 70°C Relative Humidity: 0 –100% RH Enclosure Rating: NEMA-4X enclosure, waterproof, chemical and weather resistant. Inputs 4-20 mA Accepts any 4-20 mA transmitters (24 VDC, 2 or 3 wire). Wiring distances up to 1,500 metres. Sampling methods: Diffusion and sample draw heads available. Carbon Monoxide (CO) 0 – 150 ppm, Combustibles 0 -100% LEL, Nitrogen Dioxide (NO2) 0 – 15.0 ppm (Refer to list of detectable Gases for additional ranges). Outputs Relays: 2 relays per channel 10 amp rating, SPDT isolated contacts. 1 set of common relays: 2 for gas alarm levels, 1 for malfunction. Relays fully programmable for: increasing or decreasing alarms, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off. 24 VDC: 24 VDC output provided to operate sample draw adapters or other accessories Display: 2 alphanumeric displays with backlighting. 16 characters per line; 4 lines each. All 8 channels continuously displayed. Audible: Built-in audible alarm, 94 dB, mounted on enclosure. Coded output: Pulsing = gas alarm, Steady = fail Visual: 4 visual LED alarms on front cover for alarm indications, pilot and malfunction. Optional Expansion Cards: Individual 4-20 mA (or 1-5 VDC) outputs. Heavy duty relay card (4 each @ 30 amps). Power: 240 VAC or 24 VDC. Optional – _115 VAC. Battery backup option available. Warranty: One years materials and workmanship. - Gases Detected
-
Gases Detected:
Ammonia (NH3) 0 – 75.0 ppm Arsine (AsH3) 0 – 0.2 ppm Boron Trichloride (BCl3) 0 – 15.0 ppm Carbon Dioxide (CO2) 0 – 1.0 % Carbon Monoxide (CO) 0 – 300 ppm Chlorine (Cl2) 0 – 3.0 ppm Chlorine Dioxide (ClO2) 0 – 1.0 ppm Chlorine Trifluoride (CIF3) 0 – 1.0 ppm Combustibles 0 – 100% LEL Diborane (B2H6) 0 – 30.0 ppm Fluorine (F2) 0 – 5/15 ppm Hydrogen (H2) 0 – 2000 ppm Hydrogen Chloride (HCl) 0 – 15.0 ppm Hydrogen Fluoride (HF) 0 – 9.0 ppm Hydrogen Sulfide (H2S) 0 – 100.0 ppm Nitric Oxide (NO) 0 – 100.0 ppm Nitrogen Dioxide (NO2) 0 – 15.0 ppm Nitrogen Trifluoride (NF3) 0 – 30.0 ppm Oxygen (O2) 0 – 25.0% Ozone (O3) 0 – 1.0 ppm Phosphine (PH3) 0 – 1.0 ppm Silane (SiH4) 0 – 15.0 ppm Sulphur Dioxide (SO2) 0 – 30.0 ppm TEOS (Si(OC2H5)4) 0 – 15/30 ppm - Downloads
-