Features:
- Simultaneous readout on 2 channels
- Two alarm levels per channel
- Discrete and common relays
- NEMA 4X enclosure
- 4 – 20 mA outputs
- Proven, long life sensors for a wide variety of gases
- Accepts any 4 – 20 mA transmitter input
- Easy to install, operate and expand
- Intrinsically safe design
- Min/max display
Application/s:
- Petrochemical plants
- Refineries
- Water & wastewater treatment plants
- Pulp & paper mills
- Gas, telephone & electric utilities
- Carparks
- Manufacturing facilities
- Steel
- Automotive
- HVAC
Overview:
This low cost fixed system controller is designed to accept up to two points of gas detection. It is capable of connecting directly to a variety of gas sensors. The Beacon 200 can also accept any 4-20 mA transmitter (2 or 3 wire, 24 VDC).
The Beacon 200 is capable of connecting RKI sensors directly for LEL level combustibles, oxygen, hydrogen sulphide or carbon monoxide. The Beacon 200 can also accept any 4 – 20 mA transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beacon 200 housing, or can be wired remotely from the controller.
The 10 amp rated relays are strong enough to directly power external alarms and horns without using slave relays. The digital display has backlighting and simultaneous readout of the gas type and concentration.
The Beacon 200’s housing is NEMA 4X rated for a weather tight seal and complies with lock out/tag out standards. An external reset switch allows the alarm to be silenced from outside of the controller housing. The Beacon 200 comes complete with a wall mounting kit for easy installation.
Specifications:
Physical | |
Dimensions: | Height 216mm Width 178 mm Depth: 109 mm
|
Enclosure: | Wall mounting grey polycarbonate with hinged cover
|
Conduit Connection:
|
3/4” NPT conduit hubs, 3 provided. 2 for sensor wiring and 1 for power and relay wiring |
Wiring Termination:
|
Screw type terminal block 14 gauge max
|
Power: | 240 VAC or 24 VDC. Optional – 115 VAC. Battery backup option available. |
Controls:
|
4 internal push buttons for setup, programming and calibration. 1 external push button for alarm reset.
|
Environmental
|
|
Operating Temp:
|
-20°C to 50°C
|
Storage Temp:
|
-20°C to 70°C
|
Relative Humidity:
|
0 – 100% RH
|
Enclosure Rating:
|
NEMA-4X enclosure, waterproof, chemical and weather resistant
|
Inputs | |
Direct Wired Sensors:
|
LEL/PPM Hydrocarbon, Oxygen, Carbon Monoxide, Hydrogen Sulphide, Chlorine, Sulphur Dioxide. Remote amp not required for less than 15 metres
|
4-20 mA Sensors:
|
Accepts any 4-20 mA transmitters (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. Wiring distances up to 5,000 meters
|
Sampling methods:
|
Diffusion and sample draw heads available |
Outputs
|
|
Relays:
|
4 relays – 10 amp rating, SPDT isolated contacts. 2 relays for gas alarm levels, 1 relay for malfunction. Relays fully programmable for: increasing or decreasing alarms, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off
|
4-20 mA:
|
Signal output, 4-20 mA (into 1000 ohms impedance maximum)
|
24 VDC:
|
24 VDC (350 mA max) output provided to operate sample draw adapters or other accessories
|
Display:
|
Alphanumeric display with backlighting. 20 characters per line; 4 lines each
|
Audible:
|
Built-in audible alarm, 94 dB, mounted on enclosure. Coded output: Pulsing = gas alarm, Steady = fail
|
Visual:
|
4 visual LED alarms on front cover for status indication, pilot and malfunction
|
Warranty:
|
1 year materials and workmanship
|
Gases Detected:
Ammonia (NH3) | 0 – 75.0 ppm |
Arsine (AsH3) | 0 – 0.2 ppm |
Boron Trichloride (BCl3) | 0 – 15.0 ppm |
Carbon Dioxide (CO2) | 0 – 1.0 % |
Carbon Monoxide (CO) | 0 – 300 ppm |
Chlorine (Cl2) | 0 – 3.0 ppm |
Chlorine Dioxide (ClO2) | 0 – 1.0 ppm |
Chlorine Trifluoride (CIF3) | 0 – 1.0 ppm |
Combustibles | 0 – 100% LEL |
Diborane (B2H6) | 0 – 30.0 ppm |
Fluorine (F2) | 0 – 5/15 ppm |
Hydrogen (H2) | 0 – 2000 ppm |
Hydrogen Chloride (HCl) | 0 – 15.0 ppm |
Hydrogen Fluoride (HF) | 0 – 9.0 ppm |
Hydrogen Sulfide (H2S) | 0 – 100.0 ppm |
Nitric Oxide (NO) | 0 – 100.0 ppm |
Nitrogen Dioxide (NO2) | 0 – 15.0 ppm |
Nitrogen Trifluoride (NF3) | 0 – 30.0 ppm |
Oxygen (O2) | 0 – 25.0% |
Ozone (O3) | 0 – 1.0 ppm |
Phosphine (PH3) | 0 – 1.0 ppm |
Silane (SiH4) | 0 – 15.0 ppm |
Sulphur Dioxide (SO2) | 0 – 30.0 ppm |
TEOS (Si(OC2H5)4) | 0 – 15/30 ppm |
- Overview
-
Overview:
This low cost fixed system controller is designed to accept up to two points of gas detection. It is capable of connecting directly to a variety of gas sensors. The Beacon 200 can also accept any 4-20 mA transmitter (2 or 3 wire, 24 VDC).
The Beacon 200 is capable of connecting RKI sensors directly for LEL level combustibles, oxygen, hydrogen sulphide or carbon monoxide. The Beacon 200 can also accept any 4 – 20 mA transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beacon 200 housing, or can be wired remotely from the controller.
The 10 amp rated relays are strong enough to directly power external alarms and horns without using slave relays. The digital display has backlighting and simultaneous readout of the gas type and concentration.
The Beacon 200’s housing is NEMA 4X rated for a weather tight seal and complies with lock out/tag out standards. An external reset switch allows the alarm to be silenced from outside of the controller housing. The Beacon 200 comes complete with a wall mounting kit for easy installation.
- Specifications
-
Specifications:
Physical Dimensions: Height 216mm Width 178 mm Depth: 109 mm Enclosure: Wall mounting grey polycarbonate with hinged cover Conduit Connection: 3/4” NPT conduit hubs, 3 provided. 2 for sensor wiring and 1 for power and relay wiring Wiring Termination: Screw type terminal block 14 gauge max Power: 240 VAC or 24 VDC. Optional – 115 VAC. Battery backup option available. Controls: 4 internal push buttons for setup, programming and calibration. 1 external push button for alarm reset. Environmental Operating Temp: -20°C to 50°C Storage Temp: -20°C to 70°C Relative Humidity: 0 – 100% RH Enclosure Rating: NEMA-4X enclosure, waterproof, chemical and weather resistant Inputs Direct Wired Sensors: LEL/PPM Hydrocarbon, Oxygen, Carbon Monoxide, Hydrogen Sulphide, Chlorine, Sulphur Dioxide. Remote amp not required for less than 15 metres 4-20 mA Sensors: Accepts any 4-20 mA transmitters (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. Wiring distances up to 5,000 meters Sampling methods: Diffusion and sample draw heads available Outputs Relays: 4 relays – 10 amp rating, SPDT isolated contacts. 2 relays for gas alarm levels, 1 relay for malfunction. Relays fully programmable for: increasing or decreasing alarms, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off 4-20 mA: Signal output, 4-20 mA (into 1000 ohms impedance maximum) 24 VDC: 24 VDC (350 mA max) output provided to operate sample draw adapters or other accessories Display: Alphanumeric display with backlighting. 20 characters per line; 4 lines each Audible: Built-in audible alarm, 94 dB, mounted on enclosure. Coded output: Pulsing = gas alarm, Steady = fail Visual: 4 visual LED alarms on front cover for status indication, pilot and malfunction Warranty: 1 year materials and workmanship - Gases Detected
-
Gases Detected:
Ammonia (NH3) 0 – 75.0 ppm Arsine (AsH3) 0 – 0.2 ppm Boron Trichloride (BCl3) 0 – 15.0 ppm Carbon Dioxide (CO2) 0 – 1.0 % Carbon Monoxide (CO) 0 – 300 ppm Chlorine (Cl2) 0 – 3.0 ppm Chlorine Dioxide (ClO2) 0 – 1.0 ppm Chlorine Trifluoride (CIF3) 0 – 1.0 ppm Combustibles 0 – 100% LEL Diborane (B2H6) 0 – 30.0 ppm Fluorine (F2) 0 – 5/15 ppm Hydrogen (H2) 0 – 2000 ppm Hydrogen Chloride (HCl) 0 – 15.0 ppm Hydrogen Fluoride (HF) 0 – 9.0 ppm Hydrogen Sulfide (H2S) 0 – 100.0 ppm Nitric Oxide (NO) 0 – 100.0 ppm Nitrogen Dioxide (NO2) 0 – 15.0 ppm Nitrogen Trifluoride (NF3) 0 – 30.0 ppm Oxygen (O2) 0 – 25.0% Ozone (O3) 0 – 1.0 ppm Phosphine (PH3) 0 – 1.0 ppm Silane (SiH4) 0 – 15.0 ppm Sulphur Dioxide (SO2) 0 – 30.0 ppm TEOS (Si(OC2H5)4) 0 – 15/30 ppm - Downloads
-