Features:
- 4-20 mA (3 wire) or 0-10 VDC output, selectable via jumper
- 24V AC / DC power supply
- Measures 0 – 2000 ppm
- Up to 15 years life time
- Non-dispersive infrared detector (NDIR)
Application/s:
- Office premises
- Airports
- Hotels
- Conference rooms
- Hospitals
- Schools
Overview:
Ventilation control by CO2 is a viable and energy efficient way of controlling ventilation to target cfm / person levels based on actual occupancy. The measurable rather than traditional approach of providing fixed ventilation is based on maximum occupancy. Designed for HVAC, ventilation systems, offices and other public places, this wall mounted transmitter uses NDIR technology and features a patented self-calibration system to guarantee the long term stability and up to 15 year life span.
Specifications:
Gas Detected: | Carbon Dioxide (CO2) |
Sensing Element: | Non-Dispersive Infrared Detector (NDIR) |
Accuracy @ 25°C, 2000ppm: | + 40ppm + 3% reading |
Stability: | < 2% of FS over life of sensor (15 year typical) |
Calibration Interval: | ABC Logic Self Calibration System |
Response time: | < 2 minutes for 90% step change |
Warm up time: | 2 hours (first time), 2 minutes (operation) |
CO2 measuring range: | 0 – 2000 ppm |
Sensor life: | Up to 15 years |
Power Supply: | 24V AC / 24V DC |
Consumption: | 1.5 W max; 0.8 W avg |
Analog outputs: | 0 – 10V AC or 4 – 20mA selectable by jumpers |
Relay output: | 1 x 3A switch load
Four set points selectable by jumpers |
Operating conditions: | 0-50°C; 0-95% RH, non condensing |
Weight: | 180g |
Dimensions: | 100mm x 80mm x 28mm |
Approval: | CE-Approval |
- Overview
-
Overview:
Ventilation control by CO2 is a viable and energy efficient way of controlling ventilation to target cfm / person levels based on actual occupancy. The measurable rather than traditional approach of providing fixed ventilation is based on maximum occupancy. Designed for HVAC, ventilation systems, offices and other public places, this wall mounted transmitter uses NDIR technology and features a patented self-calibration system to guarantee the long term stability and up to 15 year life span.
- Specifications
-
Specifications:
Gas Detected: Carbon Dioxide (CO2) Sensing Element: Non-Dispersive Infrared Detector (NDIR) Accuracy @ 25°C, 2000ppm: + 40ppm + 3% reading Stability: < 2% of FS over life of sensor (15 year typical) Calibration Interval: ABC Logic Self Calibration System Response time: < 2 minutes for 90% step change Warm up time: 2 hours (first time), 2 minutes (operation) CO2 measuring range: 0 – 2000 ppm Sensor life: Up to 15 years Power Supply: 24V AC / 24V DC Consumption: 1.5 W max; 0.8 W avg Analog outputs: 0 – 10V AC or 4 – 20mA selectable by jumpers Relay output: 1 x 3A switch load Four set points selectable by jumpers
Operating conditions: 0-50°C; 0-95% RH, non condensing Weight: 180g Dimensions: 100mm x 80mm x 28mm Approval: CE-Approval - Downloads
-